Bathroom Exhaust Fan CFM Calculator and Chart

As an Amazon Affiliate we earn from qualifying purchases. All earnings are directly reinvested into this site to bring you free tutorials and project files - Thank you for your support!

A bathroom exhaust fan is sized in cubic feet per minute (CFM), and the industry rule is simple: for a bathroom up to 100 sq ft, about 1 CFM per square foot of floor, never less than 50 CFM; for a larger bathroom, add up the fixtures. The calculator below applies the Home Ventilating Institute (HVI) guidance to your room, checks the air changes per hour for tall ceilings, and the chart covers common bathroom sizes. Further down: how to read the airflow and sones on the box, what ENERGY STAR requires, and where the fan should go.

Bathroom exhaust fan CFM calculator

Fixtures only count for rooms over 100 sq ft. For a smaller bathroom the floor area decides, whatever is in it.

Bathroom fan CFM chart by room size

BathroomFloor areaFan size (HVI)Air changes per hour, 8 ft ceilingFor 8 air changes at a 9 ft ceiling
5 x 7 ft35 sq ft50 CFM10.742 CFM
5 x 8 ft40 sq ft50 CFM9.448 CFM
5 x 9 ft45 sq ft50 CFM8.354 CFM
6 x 8 ft48 sq ft50 CFM7.858 CFM
6 x 9 ft54 sq ft54 CFM7.565 CFM
7 x 9 ft63 sq ft63 CFM7.576 CFM
7 x 10 ft70 sq ft70 CFM7.584 CFM
8 x 10 ft80 sq ft80 CFM7.596 CFM
8 x 12 ft96 sq ft96 CFM7.5116 CFM
9 x 11 ft99 sq ft99 CFM7.5119 CFM
10 x 10 ft100 sq ft100 CFM7.5120 CFM
Fan size = 1 CFM per sq ft, minimum 50 CFM (HVI, bathrooms under 100 sq ft). Air changes per hour = CFM x 60 / room volume. Last column = volume x 8 / 60, our arithmetic for rooms with 9 ft ceilings.

The 50 CFM floor is why a small powder room or a 5 x 7 ft bathroom still gets a 50 CFM fan. HVI’s bathroom page puts it slightly differently, with a worked example in which a 40 sq ft bathroom takes a 40 CFM fan, while its sizing table gives 50 CFM as the minimum. We follow the table and use 50 CFM as the minimum throughout; the larger fan also leaves some margin for airflow lost in the duct.

Why 1 CFM per sq ft? HVI bases the rule on about eight air changes per hour, which is what 1 CFM per sq ft gives in a room with an 8 ft ceiling: an 8 x 10 ft bathroom holds 640 cu ft of air, and 80 CFM replaces it in 8 minutes. If your ceiling is higher, or vaulted, the same rule gives fewer air changes, so size up using the last column of the chart or the calculator.

Bathrooms over 100 sq ft: add up the fixtures

FixtureExhaust rate (HVI)
Toilet50 CFM
Shower50 CFM
Bathtub50 CFM
Jetted tub100 CFM
HVI recommended intermittent rates for bathrooms over 100 sq ft. An enclosed toilet room should have its own fan (HVI notes it needs an operable window or a fan).
Example bathroomAreaFixture totalHow to split it
12 x 10 ft, toilet, tub/shower combination120 sq fttoilet 50 + tub 50 = 100 CFMOne fan over the tub, or one central fan
12 x 12 ft, toilet, separate shower and tub144 sq ft50 + 50 + 50 = 150 CFMFans over the shower and tub, or one 150 CFM fan
14 x 12 ft, enclosed toilet room, shower, jetted tub168 sq ft50 + 50 + 100 = 200 CFMA fan in the toilet room plus one or two over the wet areas
20 x 12 ft, enclosed toilet, shower, tub (HVI’s example)240 sq ft50 + 50 + 50 = 150 CFMHVI: three 50 CFM fans, or one 150 CFM fan
Fixture totals from the HVI rates above; the 20 x 12 ft case is HVI’s own worked example.

HVI gives two ways to deliver the total: several smaller fans, each placed where the moisture is made (over the shower, over the tub, in the toilet room), or one larger fan in a central spot that pulls air across the whole room. Several fans put the exhaust where it is needed and only run when that part of the room is used; one fan is cheaper to install but needs to be placed so it does not just pull air straight from the door.

Reading the box: airflow at 0.1 and 0.25 in. w.g.

Fan airflow is measured against a resistance called static pressure, given in inches of water gauge (in. w.g.). The number printed largest on most boxes is the airflow at 0.1 in. w.g., which is a short, smooth duct. A real installation, with a few feet of flexible duct, an elbow or two and a roof or wall cap with a damper, usually pushes the fan harder, and its airflow falls. ENERGY STAR deals with this directly: a certified bathroom fan must still deliver at least 70% of its 0.1 in. airflow at 0.25 in. w.g. So a fan sold as 80 CFM that is ENERGY STAR certified keeps at least 56 CFM at the higher pressure; a non-certified fan may lose more.

If the box lists airflow at 0.25 in. w.g., size from that number. If it does not, and the duct run is long, choose the next size up. Keep the duct the diameter of the fan outlet or larger, keep it short, and avoid crushed or sagging flexible duct, which adds resistance quickly.

Sones and ENERGY STAR

Fan typeMinimum efficacy (CFM per watt)Maximum sound (sones)
Bathroom and utility room fans, 10 to 89 CFM2.82.0
Bathroom and utility room fans, 90 to 200 CFM3.52.0
Bathroom and utility room fans, 201 to 500 CFM (max speed)4.03.0
In-line fans (single and multi-port)3.8no limit listed
ENERGY STAR ventilating fan criteria, based on the static pressure reference measurement in the full program requirements. Fans with more than one speed must meet them at each speed.

Sones measure loudness as people hear it, and the scale is linear: a 2 sone fan sounds about twice as loud as a 1 sone fan. ENERGY STAR caps bathroom fans up to 200 CFM at 2.0 sones, and HVI describes fans meant to run continuously as typically under 1.5 sones. Quiet matters in practice: a loud fan may get switched off before the moisture has cleared. Efficacy is airflow per watt of electricity; a fan that runs continuously or for long periods uses noticeably less power at the ENERGY STAR levels.

Where to put the fan and how long to run it

  • Over or near the shower or tub. HVI says exhaust points are typically over or near the shower or tub, and in an enclosed toilet room. A fan directly over a shower must be one marked as suitable for that wet location; follow the fan maker’s wiring and installation instructions.
  • Away from the supply air. Locate the fan away from where replacement air enters, so the air sweeps across the room instead of short-circuiting from the door to the fan.
  • Leave a gap under the door. HVI calls for at least 3/4 in clearance under the bathroom door so that air can get in to replace what the fan removes.
  • Run it 20 minutes after a shower. HVI recommends at least 20 minutes after each use (20 to 30 minutes in its living-areas guide). A timer switch or humidity-sensing control makes that automatic.
  • Duct it outside. HVI’s guidance is for fans ducted to the outside. Moist air dumped into an attic or a soffit can condense on cold framing and sheathing, the kind of damage the fan is meant to prevent.
  • Steam showers need their own fan in the steam room, switched on after use (HVI).

Intermittent or continuous ventilation

HVI allows a fan that runs all the time at a minimum of 20 CFM in place of a 50 CFM fan switched on when needed. Continuous ventilation suits tight houses where the bathroom fan doubles as whole-house ventilation: a very quiet, efficient fan runs at a low speed all day and boosts when the bathroom is used. If you go that way, check the efficacy and sound rating at the low speed, since that is where the fan spends most of its time.

Worked example: 8 x 10 ft bathroom with a 9 ft ceiling

Floor area 80 sq ft, under 100 sq ft, so the HVI rule gives 80 CFM. The room holds 8 x 10 x 9 = 720 cu ft; 80 CFM changes it 80 x 60 / 720 = 6.7 times an hour. To keep eight air changes the fan would need 720 x 8 / 60 = 96 CFM, so a 100 CFM fan is the better pick, especially with a 10 ft run of duct to a roof cap. Rated at 0.1 in. w.g., an ENERGY STAR fan of that size must still give at least 70 CFM at 0.25 in.

Building codes also regulate exhaust fans, duct termination and makeup air, and they vary by state and city. HVI’s figures are industry guidance; your building department decides what is required on your job.

Related calculators

Frequently asked questions

How many CFM do I need for a bathroom fan?

1 CFM per sq ft of floor area for bathrooms up to 100 sq ft, with a 50 CFM minimum (HVI). For larger bathrooms add 50 CFM for each toilet, shower and tub and 100 CFM for a jetted tub.

Is 50 CFM enough for a bathroom?

For a bathroom of 50 sq ft or less with an 8 ft ceiling, yes. An 8 x 10 ft bathroom needs about 80 CFM.

Is 80 or 110 CFM better for a bathroom?

Match the fan to the room: 80 CFM suits about 80 sq ft at an 8 ft ceiling; choose 110 for a room near 100 sq ft, a taller ceiling or a long duct run.

What sone rating is quiet for a bathroom fan?

ENERGY STAR allows up to 2.0 sones for fans up to 200 CFM. HVI describes continuous-duty fans as typically very quiet, under 1.5 sones.

How long should a bathroom fan run after a shower?

At least 20 minutes, according to HVI. A timer or humidity control switch makes this automatic.

Can a bathroom fan vent into the attic?

HVI’s guidance assumes the fan is ducted to the outside, and venting moist air into an attic risks condensation and mould on the framing. Check your local code for where the duct must end.

Sources

  1. Home Ventilating Institute (HVI), How Much Ventilation Do I Need? (HVI ventilation guide articles; read 25 October 2026).
  2. HVI, Bathroom Ventilation (small and large rooms, fixture table, worked examples, fan location and run time).
  3. HVI, Ventilating Living Areas (eight air changes per hour basis, ducting to the outside).
  4. US EPA, ENERGY STAR, Ventilating Fans Key Product Criteria: minimum efficacy, maximum sound levels and installed performance (read 25 October 2026).

Last reviewed: 25 October 2026. Numbers in the tables are our arithmetic from the sources listed; code sections are summarised, not quoted. How we check our work: methodology and corrections. Spotted an error? Please let us know.