The number that tells you whether a tank water heater is big enough is its first-hour rating (FHR): the gallons of hot water it can deliver in one hour starting from a full, hot tank. Tank size in gallons is only part of that; how fast the burner or element reheats the water is the rest. To size a water heater, estimate the hot water your household uses in its busiest hour, usually the morning showers, and pick a model whose FHR is at least that. For a tankless heater, the figure is the flow in gallons per minute it can deliver at your temperature rise. The calculator below does both, using the federal test conditions as defaults.

Water heater size calculator

Defaults: 58°F incoming water and a 125°F tank are the conditions of the DOE water heater test; the 105°F shower is our assumption for a comfortable shower. At those temperatures a shower is 70% hot water and 30% cold. Sinks are counted at the federal maximum faucet flow of 2.2 gpm, and dishwashers at the federal maximum of 5.0 gallons per cycle (most use less; enter your model’s figure). Enter the clothes washer’s hot water from its manual, or zero for cold-water washing.

First-hour rating needed for back-to-back showers

Showers in the busiest hour1.5 gpm head1.8 gpm head2.0 gpm head2.5 gpm head (federal maximum)2.0 gpm plus a few minutes at the sink
18 gal10 gal11 gal14 gal16 gal
217 gal20 gal22 gal28 gal27 gal
325 gal30 gal34 gal42 gal39 gal
434 gal40 gal45 gal56 gal50 gal
542 gal51 gal56 gal70 gal61 gal
651 gal61 gal67 gal84 gal72 gal
Hot water at 125°F for 8-minute showers mixed to 105°F from 58°F incoming water (70% hot). Last column adds about 5 gal for sinks in the same hour. Our arithmetic; read across to your showerhead and down to the number of showers.

This is the “family of 4” answer, made explicit. If four people each take an 8-minute shower in the same morning hour with 2.0 gpm heads, the household needs about 45 gallons of hot water in that hour, so a tank heater with an FHR of 45 gallons or more. With 2.5 gpm heads it is 56 gallons. If the showers are spread across the morning and evening, the busiest hour may hold only two, and a smaller heater will do. The number of people matters less than how many of them use hot water in the same hour.

DOE usage bins: how water heaters are rated

Usage bin (draw pattern)First-hour rating, tank heatersMax flow, tankless heatersHot water drawn in the 24-hour test
Very smallunder 18 galunder 1.7 gpm10 gal
Low18 to under 51 gal1.7 to under 2.8 gpm38 gal
Medium51 to under 75 gal2.8 to under 4 gpm55 gal
High75 gal and up4 gpm and up84 gal
10 CFR 430 Subpart B, Appendix E, Tables I, II and III.1 to III.4. The bin decides which daily draw pattern a heater is tested with, and so which efficiency (UEF) figure applies.

Every residential water heater sold in the US is tested to the same federal method. Water enters at 58°F, the heater delivers it at 125°F, and in the first-hour test tank heaters are drained at 3 gpm (1.5 gpm for tanks under 20 gallons), with new draws started as the heater’s controls cycle, until the hour is up. The water delivered in that hour is the first-hour rating. Tankless heaters are rated instead by the maximum flow they can hold over a 67°F rise for 10 minutes.

The rating then puts the heater in a usage bin, and it is tested for efficiency on that bin’s daily draw pattern: 38 gallons a day for the low bin, 55 for medium, 84 for high. That is why the Uniform Energy Factor (UEF) on the label is quoted together with a bin, and why comparing the UEF of a medium-bin heater with a high-bin one is not like for like.

Tankless water heaters: flow and temperature rise

Hot water flowAt a 40°F riseAt a 60°F riseAt a 77°F rise
2 gpm42k Btu/h gas or 12 kW electric63k Btu/h gas or 18 kW electric81k Btu/h gas or 23 kW electric
3 gpm63k Btu/h gas or 18 kW electric95k Btu/h gas or 27 kW electric122k Btu/h gas or 34 kW electric
4 gpm84k Btu/h gas or 24 kW electric126k Btu/h gas or 36 kW electric162k Btu/h gas or 46 kW electric
5 gpm105k Btu/h gas or 30 kW electric158k Btu/h gas or 44 kW electric203k Btu/h gas or 57 kW electric
6 gpm126k Btu/h gas or 36 kW electric189k Btu/h gas or 53 kW electric243k Btu/h gas or 68 kW electric
8 gpm168k Btu/h gas or 47 kW electric253k Btu/h gas or 71 kW electric324k Btu/h gas or 91 kW electric
Heat needed = gpm x 500 x rise (500 = 8.33 lb per gallon x 60 minutes). Gas input at 95% efficiency, electric at 99%. 1 kW = 3,412 Btu/h. Our arithmetic.

A tankless heater has no stored hot water to fall back on, so it must heat the full flow as it passes. The load is the flow times the temperature rise, which is why the same unit delivers far fewer gallons per minute in a northern winter than in a southern summer. With 58°F water and a 125°F setting the rise is 67°F; with 40°F winter water heated to 120°F it is 80°F. Two 2.0 gpm showers at 105°F, from 40°F water heated to 120°F, need about 3.3 gpm of hot water, close to 140,000 Btu/h of gas at 95% efficiency, or about 38 kW electric, roughly 160 A at 240 V. That electrical load is the practical limit for whole-house electric tankless heaters in cold climates.

Federal fixture flow limits used above

FixtureMaximumRegulation
Showerhead2.5 gpm at 80 psi10 CFR 430.32(p)
Lavatory (bathroom) faucet2.2 gpm at 60 psi10 CFR 430.32(o)
Kitchen faucet2.2 gpm at 60 psi10 CFR 430.32(o)
Dishwasher, standard size5.0 gal per cycle10 CFR 430.32(f)
Dishwasher, compact3.5 gal per cycle10 CFR 430.32(f)
US federal efficiency standards for products manufactured after the dates in the regulation (1994 for faucets and showerheads). Many newer fixtures use less; check the flow marked on yours.

ENERGY STAR water heater criteria

TypeEfficiencyHot water delivery
Heat pump (integrated)UEF 3.30 or more (2.20 for 120 V plug-in and split systems)FHR 45 gal or more
Gas storage, over 20 to 55 galUEF 0.81 (medium draw) or 0.86 (high draw)FHR 51 gal or more
Gas storage, over 55 galUEF 0.86 or moreFHR 51 gal or more
Gas tankless (instantaneous)UEF 0.95 or moreMax flow 2.8 gpm or more over a 67°F rise
ENERGY STAR Water Heater Key Product Criteria, read 25 October 2026. Warranty and safety requirements also apply.

ENERGY STAR’s own advice for a replacement is to start from the capacity of the heater you have, from its nameplate or yellow EnergyGuide label, and go larger if people, showers or water-using appliances have been added. That is a sensible floor; the first-hour rating comparison above tells you whether the old heater was actually big enough. ENERGY STAR also notes that heat pump water heaters need a space that stays between 40 and 90°F year-round with about 1,000 cu ft of air around the unit, and that in cold weather with cold incoming water they may switch to electric resistance heating for a while, which uses more energy.

Worked example: family of four, one morning rush

Three showers between 6:30 and 7:30, each 8 minutes with 1.8 gpm heads: 3 x 1.8 x 8 = 43.2 gallons of mixed water, 70% hot, so 30.3 gallons at 125°F. Add 4 minutes of hot water at the kitchen sink (4 x 2.2 x 0.70 = 6.2 gal) and a dishwasher run started before leaving (we assume 4 gal; check your model’s figure, which cannot exceed the 5.0 gallon federal limit): about 41 gallons. A tank heater with an FHR of 41 gallons or more covers the rush, which is in the DOE low usage bin. If a fourth person showers in the same hour, it rises to about 51 gallons, the edge of the medium bin.

Other things that change the answer

  • Incoming water temperature. Groundwater and municipal supply temperatures vary with region and season. Colder water means each shower takes more hot water and each tankless gallon needs more heat. Measure it at a cold tap in winter if you can.
  • Tank temperature setting. A hotter tank stretches the stored water further because less of it is needed per shower, but it increases standby loss and scald risk; mixing valves let a tank run hotter while delivering safer water at the taps.
  • Big tubs and body sprays. A large soaking tub can take more hot water in a few minutes than several showers; enter its fill volume in the bath field.
  • Recirculation. A recirculating loop brings hot water to the tap faster but adds heat loss from the pipes; it does not change the first-hour rating you need.

Related calculators

Frequently asked questions

What size water heater do I need for a family of 4?

It depends on how many showers fall in the same hour. Four 8-minute showers at 2.0 gpm in one hour need about 45 gallons of hot water, so a tank heater with a first-hour rating of 45 gallons or more; with showers spread out, less.

What is a first-hour rating?

The gallons of hot water a tank water heater can deliver in one hour, starting fully heated, under the DOE test (58°F in, 125°F out, drawn at 3 gpm). It combines tank size and recovery speed.

Is a 40 or 50 gallon water heater better?

Compare first-hour ratings rather than tank size: a 40 gallon gas heater with fast recovery can out-deliver a 50 gallon electric one. Choose the one whose FHR covers your busiest hour.

How many gpm tankless water heater do I need?

Add the flows that run at the same time, as hot water: two 2.0 gpm showers mixed to 105°F take about 2.8 gpm of 125°F water from 58°F supply. Check that the heater delivers that at your winter temperature rise.

What do the DOE usage bins mean?

Very small, low, medium and high bins group water heaters by first-hour rating (under 18, 18 to 50, 51 to 74, 75 gallons and up). Each bin is tested on its own daily draw pattern for the efficiency rating.

Sources

  1. 10 CFR Part 430, Subpart B, Appendix E, Uniform Test Method for Measuring the Energy Consumption of Water Heaters: sections 2.3 to 2.5 (test temperatures), 5.3 (first-hour and maximum GPM tests), 5.4.1 Tables I and II (draw pattern bins), Tables III.1 to III.4 (daily volumes). US federal regulation, read at law.cornell.edu (cached 25 October 2026).
  2. 10 CFR 430.32(f), (o) and (p): dishwasher water, faucet and showerhead maximums.
  3. ENERGY STAR Water Heater Key Product Criteria and ENERGY STAR heat pump water heaters (read 25 October 2026).
  4. Shower temperature (105°F), shower length (8 minutes) and the household examples are our assumptions; the arithmetic is shown with each table.

Last reviewed: 25 October 2026. Numbers in the tables are our arithmetic from the sources listed; code sections are summarised, not quoted. How we check our work: methodology and corrections. Spotted an error? Please let us know.